Getting The System Running
Ensure all Sub-panels and Repeaters have unique addresses. Ensure all connectors are firmly in place.
Ensure that all connections are tight, with no stray strands of wire. Ensure that the SIM CARD is securely
fitted in all Main Panels, Repeaters and Standard Sub-panels
Power up all External Sub-panels and Repeaters then power up the Main Panel.
Press SYSTEM RESET.
Confirm that all standard Sub-panels have a solid green COMMS OK LED.
If the COMMS OK LED is flashing then there is no communication (via the Data Loop) to the Main Panel.
If the COMMS OK LED is solid green and the sub-panel has no other faults then the amber LOCAL FAULT
LED should be extinguished. If the LOCAL FAULT LED is lit then information on the fault should be available
at the Main Panel.
Confirm that all Repeaters are showing identical information (LEDs and LCD) to that displayed by the Main
Panel.
Press and hold LAMP TEST on the Main Panel.
All the LEDs should light, the LCD backlight should turn on and all pixels on the LCD should be black. (See
below.)
Communications Check
Main Panel Check
Ensure that the Main Panel is in Installation Mode (SYSTEM ON LED flashing). If not enter programming
mode and select function 8-4-1 Active/Installation Mode and put the panel into Installation Mode.
COMMISSIONING
All the LEDs should be illuminated. Release the LAMP TEST switch to end the test, all
LEDs should extinguish except SYSTEM ON and any active indications
FIRE ALARM SYSTEM
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
PROC. FAULT
TRANS. FAULT
SOUND ALARMS
PAPER FEED
LAMP TEST
SYSTEM RESET
DISABLED
TEST
FAULT
FIRE
AUXILIARY
RELAYS
FIRE BRIGADE
TRANSMISSION
SELECTED
DETECTORS
ACTIVE
DELAYS
FIRE BRIGADE
ACKNOWLEDGED
ALARM DISPLAY
JUNO-NET
MANUFACTURED TO THE
REQUIREMENTS OF
EN54 Pt 2 & Pt 4 1999
Comentarios a estos manuales