APPENDIX C – FAILURE CODES OF THE EN54 27,6V POWER SUPPLY
Technical
output
activation
- No AC mains supply
- F
MAIN
fuse failure
- Blown F
BAT
fuse
- Short circuit in the battery circuit
- Short circuit in the AUX1 and AUX2 output
circuit
- Worn out batteries
- Undercharged batteries
- The output voltage of the PSU over 29.2V
Battery charging circuit
failure!
- The output voltage of the PSU set too low ,
below 26V
- Battery charging circuit failure
- The output voltage below 26V
- The battery voltage has dropped below 23V
(during battery-assisted operation)
Low battery voltage –
off!
- the battery voltage has dropped below 20V
(during battery-assisted operation)
- Activation of the input of collective failure:
EXTi
Temperature sensor
failure!
- Temperature sensor failure
- Temperature sensor disconnected
- Too high ambient temperature of the PSU.
- Overloaded batteries.
- Faulty batteries.
- Deeply discharged batteries, voltage below
20V
High resistance of the.
Battery circuit!
- Worn out batteries
- Loose cables connecting the batteries
- Mains supply over 254V AC
- Mains supply below 195V AC
-----------------------------------------------------
Internal damage of the
PSU.
- no communication with LCD panel